Permit Number: T15CM07084
Parcel: 133323460

Address:
9230 E 8TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM07084
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM07084

PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
DIAGRAMS / CALCULATIONS

1. The intent of the sum of the main and backfeed breakers not exceeding 120% of the busbar rating is for bus protection from two sources, NEC 690.64 & 705.12 (D). Also, breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3.
2. All service at the 6-disco panel shall be disconnected with not more than six switches, NEC 690.14 (C). Notate these switches on the proposed 6-disco panel.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review