Permit Number: T15CM07014
Parcel: 12310001A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM07014
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Were structural calculations for the current (revised) ambulance canopy configuration reviewed by the City of Tucson for the framing and foundation? Please verify.
07/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/10/2017 STEVE SHIELDS ZONING REVIEW Approved
08/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show the size, routing, and termination of the primary and secondary condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
08/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/16/2017 LOREN MAKUS ENGINEERING REVIEW Passed