| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/26/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G101; CODE REVIEW PLAN: THE OCCUPANCY TYPE IS LISTED AS AN S-2 (PARKING GARAGE?). SHOULD THIS BE LISTED AS A UTILITY CLASSIFICATION (CARPORTS)? PLEASE VERIFY. THE S-2 CLASSIFICATION WOULD INDICATE AN OCCUPANCY LOAD WOULD BE ATTACHED TO THE USE. IS THERE A CODE ISSUE THAT WOULD BENEFIT THE S-2 CLASSIFICATION? 2. SHEET G101; CODE REVIEW PLAN: THE NEW ENTRY CANOPY REFERENCES SECTION 3015 FOR CONSTRUCTION MATERIALS. PLEASE REVISE THE CODE REFERENCE. 3. SHEET A101; SITE PLAN: A SECTION CUT BETWEEN GRIDS D AND E REFERENCES 1/A301. PLEASE REVISE THE SECTION REFERENCE. 4. SHEET A201; DEMOLITION PLAN: ADD DEMOLITION KEYNOTE 5 TO THE PLAN. 5. SHEET A301; DETAIL 8: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/27/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review | DP must be approved first. |
| 10/29/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. #1. Provide complete compliance with the Tucson Outdoor Lighting Code. #2. Provide compliance with the IECC. #3. Provide a complete luminaire schedule. #4. Provide pole base information as per keynote 6 on plan sheet E101. Ref: IBC sec 107.2.1, NEC art 408. |
| 11/02/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: BUMCT - Facility Expansion - ED Ambulance Canopy T15CM7014 Building Plan (1st Review) TRANSMITTAL DATE: November 2, 2015 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The building plans appear to match development package DP15-0185 but cannot approve the building plans until the development package has been approved by all PDSD review agencies. 3. Sheet A101, lower left corner of the sheet there is a note, "NEW AMBULANCE ENTRY SIGN" that points to the middle of the sidewalk. It appears that this sign encroaches into the sidewalk. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |