Permit Number: T15CM06995
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06995
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2015 DAVID RIVERA ZONING REVIEW Approved
10/08/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/09/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET X1.0; GENERAL BUILDING SUMMARY: FOR THE TENANT SPACE OCCUPANT LOAD, THE DINING/SERVING AREA NEEDS TO USE A FACTOR OF 15 SF/PERSON PER TABLE 1004.1.2. ALTHOUGH SECTION 303.1.1 ALLOWS THE CLASSIFICATION TO BE A B, THE OCCUPANT LOAD MUST STILL BE CALCULATED AS AN A-2. PLEASE REVISE.
2. SHEET A1.0; REFERENCE FLOOR PLAN: PER THE IBC SECTION 1109.11, ACCESSIBLE SEATING AT THE COUNTER AND THE COUNTER HEIGHT WHERE PATRONS ARE SERVED MUST ALSO HAVE AN ACCESSIBLE PORTION. PLEASE PROVIDE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/09/2015 MARTIN BROWN FIRE REVIEW Approved
10/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/09/2015 ROBERT SHERRY WATER REVIEW Completed
10/09/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed