Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM06995
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/08/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 10/09/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET X1.0; GENERAL BUILDING SUMMARY: FOR THE TENANT SPACE OCCUPANT LOAD, THE DINING/SERVING AREA NEEDS TO USE A FACTOR OF 15 SF/PERSON PER TABLE 1004.1.2. ALTHOUGH SECTION 303.1.1 ALLOWS THE CLASSIFICATION TO BE A B, THE OCCUPANT LOAD MUST STILL BE CALCULATED AS AN A-2. PLEASE REVISE. 2. SHEET A1.0; REFERENCE FLOOR PLAN: PER THE IBC SECTION 1109.11, ACCESSIBLE SEATING AT THE COUNTER AND THE COUNTER HEIGHT WHERE PATRONS ARE SERVED MUST ALSO HAVE AN ACCESSIBLE PORTION. PLEASE PROVIDE. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/09/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/09/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/09/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |