Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM06985
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/23/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 1; SHEET A-0; CODE INFORMATION: THE CURRENT IBC CODES USED BY THE CITY OF TUCSON ARE THE 2012 EDITIONS WITH AMENDMENTS. THE ELECTRICAL CODE IS THE 2011 NEC WITH AMENDMENTS. PLEASE REVISE. 2. PREVIOUS COMMENT 2; SHEETS A-0.2 AND A0.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
10/23/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The size of the previous HVAC unit is not an adequate justification. Provide a unit with adequate capacity at the local conditions to meet the calculated cooling load that is not over-sized (within the available equipment capacities). [Initial comment: Provide justification for installing an HVAC unit having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations. Reference: Section C403.2.2, IECC 2012.] |
10/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |