Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1; SHEET A-0; CODE INFORMATION: THE CURRENT IBC CODES USED BY THE CITY OF TUCSON ARE THE 2012 EDITIONS WITH AMENDMENTS. THE ELECTRICAL CODE IS THE 2011 NEC WITH AMENDMENTS. PLEASE REVISE.
2. PREVIOUS COMMENT 2; SHEETS A-0.2 AND A0.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/23/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The size of the previous HVAC unit is not an adequate justification. Provide a unit with adequate capacity at the local conditions to meet the calculated cooling load that is not over-sized (within the available equipment capacities). [Initial comment: Provide justification for installing an HVAC unit having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations. Reference: Section C403.2.2, IECC 2012.]
10/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved