Permit Number: T15CM06985
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06985
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
10/08/2015 JASON GREEN ENGINEERING REVIEW Approved
10/09/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate panel homeruns and circuiting for all light fixtures and power devices. Locate the panel locations on the power plan.
Ref: IBC 107.2.1, NEC 408
10/09/2015 MARTIN BROWN FIRE REVIEW Approved
10/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-0; CODE INFORMATION: THE CURRENT IBC CODES USED BY THE CITY OF TUCSON ARE THE 2012 EDITIONS WITH AMENDMENTS. THE ELECTRICAL CODE IS THE 2011 NEC WITH AMENDMENTS. PLEASE REVISE.
2. SHEETS A-0.2 AND A0.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
3. SHEET A0.4: PLEASE REPLOT THIS SHEET SO IT IS LEGIBLE.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/09/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/13/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. (Note that the COMcheck mechanical compliance certificate may be submitted as a separate 8.5" x 11" document) Reference: Section 107.2.1, IBC 2012.
2. Provide justification for installing an HVAC unit having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations. Reference: Section C403.2.2, IECC 2012.
3. Show that the new rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
10/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/13/2015 ROBERT SHERRY WATER REVIEW Completed