Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/08/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/08/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/09/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please designate panel homeruns and circuiting for all light fixtures and power devices. Locate the panel locations on the power plan. Ref: IBC 107.2.1, NEC 408 |
10/09/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-0; CODE INFORMATION: THE CURRENT IBC CODES USED BY THE CITY OF TUCSON ARE THE 2012 EDITIONS WITH AMENDMENTS. THE ELECTRICAL CODE IS THE 2011 NEC WITH AMENDMENTS. PLEASE REVISE. 2. SHEETS A-0.2 AND A0.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 3. SHEET A0.4: PLEASE REPLOT THIS SHEET SO IT IS LEGIBLE. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
10/09/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. (Note that the COMcheck mechanical compliance certificate may be submitted as a separate 8.5" x 11" document) Reference: Section 107.2.1, IBC 2012. 2. Provide justification for installing an HVAC unit having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations. Reference: Section C403.2.2, IECC 2012. 3. Show that the new rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. |
10/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/13/2015 | ROBERT SHERRY | WATER | REVIEW | Completed |