Permit Number: T15CM06978
Parcel: 13015001A

Address:
4646 E 22ND ST

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T15CM06978
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2015 MARTIN BROWN FIRE REVIEW Approved
10/23/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CS (PROJECT DATA); ALLOWABLE AREA ANALYSIS: THE ALLOWABLE AREA ANALYSIS INDICATES A 68% INCREASE DUE TO THE FRONTAGE PLUS THE 300% INCREASE FOR THE SPRINKLER SYSTEM. PLEASE INDICATE ON THE DRAWING THE 300% INCREASE IN THE ALLOWABLE AREA DUE TO THE SPRINKLER SYSTEM INCREASE PER THE IBC SECTION 506.3.
2. SHEET CS; PROJECT DATA: PLEASE INDICATE ON THE DRAWING THE OCCUPANT LOAD ANALYSIS FOR THE NEW BUILDING, AND THE TOTAL OCCUPANT LOAD FOR THE EXISTING BUILDING. IT IS NOT CLEAR ON THE DRAWINGS HOW MUCH SQUARE FOOTAGE IS INCLUDED IN THE NEW ADDITION.
3. SHEET CS; PROJECT DATA (PLUMBING FIXTURES): A NOTE UNDER THE PLUMBING FIXTURE TABLE INDICATES THERE ARE TWO URINALS IN THE MEN'S RESTROOM IN LIEU OF ONE WATER CLOSET. PER THE IPC SECTION 419.2, URINALS SHALL NOT BE SUBSTITUTED FOR MORE THAN 50% OF THE REQUIRED WATER CLOSETS IN ALL OCCUPANCIES EXCEPT ASSEMBLY AND EDUCATIONAL. IF THREE WATER CLOSETS ARE REQUIRED, ONLY ONE URINAL MAY BE SUBSTITUTED.
4. SHEET CS; PROJECT DATA (PLUMBING FIXTURES): PLEASE PROVIDE ON THE DRAWINGS THE CALCULATIONS FOR THE PLUMBING FIXTURES REQUIRED FOR THE OCCUPANT LOAD REQUESTED IN COMMENT 2.
5. SHEET CS; PROJECT DATA (BUILDING AREA CALCULATIONS): AN ACTUAL BUILDING SQUARE FOOTAGE IS LISTED AS 32,178 SF, BUT THE BUILDING AREA CALCULATIONS INDICATE 31,415 SF. PLEASE CLARIFY. IS THIS THE AREA FOR THE BUILDING INCLUDED IN THIS TENANT IMPROVEMENT (ALONG WITH EXISTING BUILDING SF)?
6. SHEET CA1.00: PLEASE INDICATE ON THE PLANS THAT THE REQUIREMENT OF THE IBC SECTION 1105.1 (60% OF PUBLIC ENTRANCES ARE ACCESSIBLE) IS MET FOR THIS BUILDING.
7. SHEET CA1.00: PLEASE INDICATE ON THE PLANS THAT THE SIGNAGE REQUIRED BY THE IBC SECTION 1110.1(4) IS PROVIDED. INDICATE ON THE PLAN WHERE THESE SIGNS ARE LOCATED.
8. SHEET CA1.00; PLANS 1 AND 2: PLEASE REVISE THE TITLES OF THE TWO PLANS.
9. SHEET A1.01; FLOOR PLAN: A BUILDING SECTION 3/A5.00 IS CUT ON THE PLAN. SHOULD THIS BE 4/A5.00? VERIFY.
10. SHEET A1.02; FLOOR PLAN: THE MATCH LINE AT THE WEST END REFERENCES SHEET A1.02. PLEASE REVISE THE SHEET REFERENCE.
11. SHEET A1.02; FLOOR PLAN: AT THE RETAIL PARTS AREA (108), A RETAIL COUNTER (KEYNOTE 118) INDICATES A HEIGHT OF +42". PER THE ICC/ANSI SECTION 904.3, THE MAXIMUM HEIGHT OF THE COUNTER ABOVE FINISH FLOOR IS 36" TO MEET ACCESSIBILITY REQUIREMENTS. PLEASE REVISE.
12. SHEETS A4.00, A4.01, A5.00, AND A5.01: A NOTE FOR FINISHES INDICATES TO SEE SHEETS FL1.00 OR FL1.01 FOR FINISH LEGEND. PLEASE REVISE THE SHEET REFERENCE.
13. SHEET A6.00; INTERIOR ELEVATIONS 11 AND 12: THE TECHNICAL PARTS COUNTER INDICATES A HEIGHT OF
3'-6". PER THE ICC/ANSI SECTION 904.3, THE MAXIMUM HEIGHT OF THE COUNTER ABOVE FINISH FLOOR IS 36" TO MEET ACCESSIBILITY REQUIREMENTS. PLEASE REVISE.
14. SHEET A7.00; EAST ENTRANCE RAMP: THE KEYNOTE 144 IS REFERENCED AT THE RAMP AREA AND THE STAIR AREA, BUT THE NOTE INDICATES THE HANDRAIL AT 2'-10" ABOVE THE STAIR NOSING. PLEASE REVISE THE NOTE TO INCLUDE THE RAMP.
15. SHEET S3.1; ROOF FRAMING PLAN: AT GRIDS 1.8 AND F.3, A DETAIL CUT REFERENCES 207. PLEASE REVISE THE DETAIL REFERENCE.
16. SHEET S4.1; DETAIL 107: NOTE 7 INDICATES 4-#4 CONTINUOUS. ONLY THREE ARE INDICATED. PLEASE VERIFY.
17. SHEET S4.1; DETAIL 109: NOTE 7 INDICATES 3-#4 CONTINUOUS. SHOULD THIS BE 5? PLEASE VERIFY.
18. SHEET S4.1; DETAIL 112: NOTE 4 IS NOT INDICATED ON THE DETAIL. PLEASE ADD.
19. SHEET S4.1; DETAIL 115: PLEASE INDICATE NOTE 5 IN THE NOTES.
20. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
#1. Could not locate plan sheet E0.40 as listed on the cover sheet index.
#2. Lumenaires designated as 'FL', 'J', 'R', ( lighting plans ) are not shown on the lighting schedule.
#3. The exterior lighting source output color temperature not to exceed 3500K as per sec. 402.1 of the Tucson Outdoor Lighting Code.
#4. There are two electrical plan sheets with the same index E0.20, and not listed on the cover plan sheet index.
Ref : IBC sec. 107.2.1
10/26/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Chapman Audi
T15CM6978
Building Plan (2nd Review)

TRANSMITTAL DATE: October 26, 2015

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans appear to match development package DP15-0130 but cannot approve the building plans until the development package has been approved by all PDSD review agencies.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/26/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
10/29/2015 LOREN MAKUS ENGINEERING REVIEW Approved
11/04/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the automatic lavatory faucets will operate for a minimum time of 10-seconds. Reference: Section 606.4, ICC/ANSI A117.1-03.
2. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012.
11/04/2015 ROBERT SHERRY WATER REVIEW Completed
11/05/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the balancing data for exhaust fan EF-A1. It is scheduled for 450 CFM on sheets M2.00 and M2.01 but the balancing data on sheet M1.01 shows a total air flow of 550 CFM. Reference: Section 107.2.1, IBC 2012.
2. Clarify the Envelope Compliance Certificate with regard to the type of wall insulation being used. Most of the exterior wall types (e.g. E, F, H, and K) appear to be built with cavity insulation, not continuous insulation. Include the wall type designation on the component description in COMcheck. Reference: Section C103.2, IECC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the new heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2015 ANY REJECT SHELF RECEIVED