Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T15CM06945
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/10/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The structural drawings and calculations do not appear to include the two rooftop units. [Initial comment: Verify that the installation of the two rooftop units will not adversely affect the structural integrity of the roof. Reference: Section 302.1, IMC 2012.] 2. The submitted portable welding fume extractors provide particulate filtration and remove the welding fumes from the location of the welder but do not provide exhaust for the room. Reference: sections 403.3 and 501.3, IMC 2012. [Initial comment: Clarify the reason for not providing general exhaust for the welding lab and the electronics lab based on the requirements of Table 403.3, IMC 2012 and local exhaust for tools that produce fumes, dust, smoke or other irritating substances. Reference: Sections 403.3 and 502.1, IMC 2012.] |
11/10/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The fixture calculations on sheet G-1 do not show that adequate plumbing facilities are available. [Initial comment: Show how the minimum required plumbing facilities are being provided. Reference: Section 2902.1, IBC 2012.] |
11/12/2015 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review |