Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM06945
Parcel: 14002010A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM06945
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2015 KEN BROUILLETTE FIRE REVIEW Approved
10/27/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
10/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-1; GENERAL BUILDING SUMMARY TABLE: UNDER THE USES, IT IS LISTED THAT THIS BUILDING HAS SEPARATED USES. PLEASE REVIEW SECTION 508 OF THE IBC AND VERIFY THIS PROJECT HAS SEPARATED OCCUPANCIES.
2. SHEET G-1; GENERAL BUILDING SUMMARY TABLE: A NOTE AT THE BOTTOM OF THIS TABLE INDICATES NO FIRE SEPARATIONS NEEDED PER THE IBC TABLE 508.4. PLEASE COORDINATE WITH COMMENT 1.
3. SHEET G-1; CODE CHECK: PLEASE PROVIDE THE CALCULATIONS ON THIS SHEET FOR THE REQUIRED NUMBER OF PLUMBING FIXTURES IN THIS BUILDING (WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS) PER THE IBC TABLE 2902.1. RESTROOMS ARE NOT INDICATED ON THE PLAN.
4. SHEET S2.1; NOTE: A NOTE ON THIS SHEET INDICATES FOUNDATION DESIGNS ARE BASED ON PRELIMINARY METAL BUILDING REACTIONS. PLEASE REVIEW THE REACTIONS AND REVISE THIS NOTE SINCE THE FINAL BUILDING DESIGN IS INCLUDED WITH THIS SUBMITTAL.
5. SHEET S3.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE TABLES AND BAR DETAILS.
6. SHEET S3.1; DETAIL 102: PLEASE ADD NOTE 4 TO THE DETAIL NOTES.
7. SHEET A-1; FLOOR PLAN: KEYED NOTE 14 INDICATES A NEW WATER COOLER, AND REFERENCES P-SHEETS FOR THE SPECIFICATION. A WATER COOLER IS INDICATED ON SHEET P-1, BUT NO SPECIFICATIONS ARE PROVIDED. THIS MUST BE A HIGH/LOW DRINKING FOUNTAIN, OR A SINGLE POINT OF USE WATER DISPENSER CONNECTED DIRECTLY TO A WATER LINE. PLEASE PROVIDE.
8. SHEET A-2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE GRID LINES.
9. SHEET A-2; BUILDING ELEVATION KEYED NOTES: NOTE 5 WAS NOT LOCATED ON THE ELEVATIONS. PLEASE VERIFY.
10. SHEET A-3; BUILDING SECTION KEYED NOTES: THE TITLE OF THE KEYED NOTES INDICATES BUILDING ELEVATION KEYED NOTES. PLEASE REVISE THE TITLE.
11. SHEET A-3; BUILDING SECTION KEYED NOTES: NOTES 5 AND 6 WERE NOT LOCATED ON THE SECTIONS. PLEASE VERIFY.
12. SHEETS B1 THROUGH B24: THESE SHEETS INCLUDE THE DRAWINGS FOR THE PREFABRICATED METAL BUILDING. PER THE IBC SECTION 107.3.4.1, THESE DOCUMENTS, ALONG WITH THE STRUCTURAL CALCULATIONS, SHALL BE SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE, WHO WILL IN TURN INDICATE ON THE DRAWINGS AND CALCULATIONS THE SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO THE BUILDING DESIGN. AT THAT POINT, THE DOCUMENTS SHALL BE SUBMITTED TO THE CITY OF TUCSON FOR REVIEW. THIS REVIEW DOES NOT INCLUDE THE PREFABRICATED METAL BUILDING DOCUMENTS.
13. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/30/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/03/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the site improvements to the water service shown on sheet C-1 (e.g. size of pipe, material of construction, etc.). Reference: Section 107.2.1, IBC 2012.
2. Clarify the installation of the new building sewer running between the new building and the existing building. Provide the material of the pipe, the inverts, the slope, and the location of the proposed backwater valve. Explain the purpose of the two-way cleanout at the entrance to the existing building. Reference: Section 107.2.1, IBC 2012.
3. Show how the minimum required plumbing facilities are being provided. Reference: Section 2902.1, IBC 2012.
4. Clarify how hot water is being supplied to the service sink (P-1). Reference: Section 607.1, IPC 2012.
5. Verify that the gutter sections slope at least 1/8" per foot toward the downspouts. Reference: Section 1106.6, IPC 2012
11/03/2015 ROBERT SHERRY WATER REVIEW Completed
11/04/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the U-values for the exterior doors noted on the Envelope Compliance Certificate with the door schedule shown on the drawings. Reference: Section C103.2, IEC 2012.
2. Coordinate the air conditioning load calculations with the mechanical design shown on sheets M1 and M2 (e.g. two heat pumps and more ventilation loads). Reference: Section C403.2, IECC 2012.
3. Verify that the installation of the two rooftop units will not adversely affect the structural integrity of the roof. Reference: Section 302.1, IMC 2012.
4. Clarify the reason for not providing general exhaust for the welding lab and the electronics lab based on the requirements of Table 403.3, IMC 2012 and local exhaust for tools that produce fumes, dust, smoke or other irritating substances. Reference: Sections 403.3 and 502.1, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2015 AROMERO4 OUT TO CUSTOMER Completed