Permit Number: T15CM06936
Parcel: 116022300

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM06936
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM06936

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray tight to the roof sheathing or rigid board sealed to roof framing), R806.5. This condensation control provision is necessary for code compliance and may be layered with batt insulation for achieving the total required roof R-value. Update roof details sheet A3.

PLUMBING PLANS:

1. Show hot water pipe with minimum R-3 insulation, N1103.4.2.

MECHANICAL PLANS:

1. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1. All other ducts outside of the thermal envelope require R-6 insulation. Update Duct Work notation sheet M1.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Update the maximum "U" factors of the windows and doors on sheet D1 as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2015 EGALLET1 OUT TO CUSTOMER Completed