Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/06/2015 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Reqs Change SEE STRUCTURAL COMMENTS.
10/06/2015 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Reqs Change SEE STRUCTURAL COMMENTS.
10/06/2015 ENEWCOM1 FIRE REVIEW Reqs Change SEE STRUCTURAL COMMENTS.
10/06/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: IT IS NOT CLEAR FROM THE DRAWINGS WHAT THIS PROJECT ENTAILS. ARCHITECTURALLY, THERE IS NO CODE ANALYSIS FOR THE WEST PORTION OF THE BUILDING (OCCUPANCY LOAD, REQUIRED EXITS, MEANS OF EGRESS, REQUIRED PLUMBING FIXTURES, TRAVEL DISTANCES, DEAD END CORRIDORS, ETC.). A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED FOR THIS SPACE. THE MECHANICAL, PLUMBING, AND ELECTRICAL ISSUES ARE NOT CLEAR. NEW REQUIREMENTS FOR THE PLUMBING FIXTURES, MECHANICAL SYSTEMS, AND NEW ELECTRICAL REQUIREMENTS MUST BE INCLUDED ON THE PLANS. FIRE REQUIREMENTS MUST BE REVIEWED AND INCLUDED ON THE PLANS.
2. GENERAL: THE PLAN IS CREATING TWO TENANT SPACES, THEREFORE REQUIRING TWO SEPARATE PERMITS. IF THE EAST SPACE IS NOT OCCUPIED AT THIS TIME, IT CAN BE PERMITTED AS A SHELL SPACE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/06/2015 ENEWCOM1 WATER REVIEW Reqs Change SEE STRUCTURAL COMMENTS.
10/06/2015 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Reqs Change SEE STRUCTURAL COMMENTS.