Permit Number: T15CM06905
Parcel: 117033090

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06905
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.
10/06/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the configuration of the ductwork for FC-5 to avoid using the egress corridor as a duct.
2. Show the size, route, and termination of the condensate waste from DAC-1.
10/06/2015 ROBERT SHERRY WATER REVIEW Reqs Change Verify the plan to use the existing 3/4" water meter for the new demand.
10/08/2015 DAVID RIVERA ZONING REVIEW Approved
10/08/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/08/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/08/2015 MARTIN BROWN FIRE REVIEW Approved
10/08/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/08/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed