Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM06905
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review. |
| 10/06/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the configuration of the ductwork for FC-5 to avoid using the egress corridor as a duct. 2. Show the size, route, and termination of the condensate waste from DAC-1. |
| 10/06/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the plan to use the existing 3/4" water meter for the new demand. |
| 10/08/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/08/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 10/08/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/08/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/08/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |