Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM06884
Parcel: 13323164A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06884
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2016 STEVE SHIELDS ZONING REVIEW Approved
01/06/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/06/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/06/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
01/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/06/2016 ROBERT SHERRY WATER REVIEW Approved
01/06/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/06/2016 KEN BROUILLETTE FIRE REVIEW Approved
01/06/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed