Permit Number: T15CM06859
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06859
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE VERIFY ALL LETTERING ON ALL SHEETS OF THIS PROJECT MEETS THAT REQUIREMENT. SEVERAL SHEETS (D101, A101, A103, A104, ETC.) HAVE LETTERING THAT DOES NOT MEET THE 3/32" HEIGHT REQUIREMENT.
2. GENERAL: PLEASE PROVIDE A WRITTEN RESPONSE TO COMMENT 1.
03/02/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide circuit and panel designation for the new pendant luminaires shown on plan sheet A111, Keynote #4.
If utilizing the existing lighting circuit and switching, please specify on the plans.
Ref: IBC sec. 107.2.1, NEC art. 408.4
10/05/2015 KEN BROUILLETTE FIRE REVIEW Approved
11/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/02/2015 ROBERT SHERRY WATER REVIEW Completed
11/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed