Permit Number: T15CM06858
Parcel: 115151210

Address:
516 W LESTER ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM06858
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide correct information for the Tucson Outdoor Lighting Calc's. Total area in acres.
#2. Indicate locations for the water heaters on the floor plans.
#3. Provide for a GFI protected main circuit breaker at the service equip. NEC art. 230.95.
#4. Provide complete panel schedules for all panels.
Ref: IBC sec. 107.2.1. 2011 NEC.
02/19/2016 KROBLES1 MECHANICAL-COMMERCIAL REVIEW Needs Review
02/19/2016 KROBLES1 ZONING REVIEW Needs Review
02/19/2016 KROBLES1 ENGINEERING REVIEW Needs Review
02/19/2016 KROBLES1 PLUMBING-COMMERCIAL REVIEW Needs Review
02/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved