Permit Number: T15CM06858
Parcel: 115151210

Address:
516 W LESTER ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM06858
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change REVISE TWO ISSUES. BERNARD HAS NOTED ON PREVIOUS COMMENT LETTER.
02/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the component descriptions in the Envelope Compliance Certificate so that they correspond to the components shown on in the drawing set. Reference: Section C103.2, International Energy Conservation Code 2012.
02/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide information to show how the proposed water heaters are to be supported from the building structure. Reference: Section 301.2, IPC 2012.
02/12/2016 MARTIN BROWN FIRE REVIEW Approved
02/16/2016 EGALLET1 ZONING REVIEW Needs Review
02/16/2016 EGALLET1 ENGINEERING REVIEW Needs Review
02/16/2016 EGALLET1 ELECTRICAL-COMMERCIAL REVIEW Needs Review