Permit Review Detail
Review Status: Completed
Review Details: REVISION - WALK THRU
Permit Number - T15CM06573
Review Name: REVISION - WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. #1. Provide compliance with NEC art. 450.14 For the 15 KVA transformer. ( Primary Feeder Disconnect Within Site ). #2. Provide compliance with NEC art. 408.36 B and D, for the new panel 'LP-EMD'. ( Main Ckt. Breaker ). |