Permit Number: T15CM06516
Parcel: 126191950

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06516
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2015 DAVID RIVERA ZONING REVIEW Approved
09/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how the Type II hood is connected to the building structure.
2. Show the installation of the exhaust duct and the exhaust fan.
09/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/18/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1; CODE CHECK: THE OCCUPANT LOAD IS LISTED AS 88, BUT THE EXITING IS LISTED AS ONE REQUIRED. PLEASE EXPLAIN HOW ONE EXIT MEETS THE IBC REQUIREMENTS OF TABLE 1015.1.
2. SHEET G1; CODE CHECK: PLEASE INDICATE ON THE DRAWINGS IF THE BUILDING IS SPRINKLERED.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/18/2015 ROBERT SHERRY WATER REVIEW Reqs Change A 5/8" water meter is limited to a demand of 15 GPM but the building appears to have a maximum demand greater than 34 GPM. Contact Tucson Water to arrange for a new meter.
09/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a riser diagram to show the new waste and vent plumbing.
2. The minimum capacity for a hydromechanical grease interceptor is 25 GPM with 50 pounds of grease capacity. Provide a detail showing how it is to be installed.
3. Specify the valves to be used for the shower.
09/18/2015 MARTIN BROWN FIRE REVIEW Approved
09/18/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed