Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM06516
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/18/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show how the Type II hood is connected to the building structure. 2. Show the installation of the exhaust duct and the exhaust fan. |
| 09/18/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/18/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 09/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1; CODE CHECK: THE OCCUPANT LOAD IS LISTED AS 88, BUT THE EXITING IS LISTED AS ONE REQUIRED. PLEASE EXPLAIN HOW ONE EXIT MEETS THE IBC REQUIREMENTS OF TABLE 1015.1. 2. SHEET G1; CODE CHECK: PLEASE INDICATE ON THE DRAWINGS IF THE BUILDING IS SPRINKLERED. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/18/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | A 5/8" water meter is limited to a demand of 15 GPM but the building appears to have a maximum demand greater than 34 GPM. Contact Tucson Water to arrange for a new meter. |
| 09/18/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a riser diagram to show the new waste and vent plumbing. 2. The minimum capacity for a hydromechanical grease interceptor is 25 GPM with 50 pounds of grease capacity. Provide a detail showing how it is to be installed. 3. Specify the valves to be used for the shower. |
| 09/18/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/18/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |