Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM06501
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A.1; FLOOR PLAN: PER OUR PREVIOUS DISCUSSION, THE COMMON PATH OF EGRESS TRAVEL MUST MEET THE REQUIREMENTS OF THE IBC TABLE 1014.3. SINCE THE OCCUPANT LOAD IS 31, THE DISTANCE TO THE EXIT MUST BE LESS THAN 75'. IF THE OCCUPANT LOAD COULD BE REDUCED TO 30 (TAKE OUT THE AREAS ASSOCIATED WITH THE RESTROOMS), THEN THE ALLOWABLE DISTANCE FOR THE COMMON PATH OF EGRESS TRAVEL CAN BE INCREASED TO 100'. THIS PLAN WOULD BE APPROVED. REMEMBER THE DISTANCE MUST BE MEASURED PER THE IBC SECTION 1016.3 (ONLY VERTICAL AND HORIZONTAL MEASUREMENTS). |
| 09/29/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/30/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |