Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM06501
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/24/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the hazard rating for a hydroculator and verify that the proposed ASSE 1024-listed backflow preventer is appropriate. [Initial comment: Provide backflow protection for all appliances that are directly-connected to water (e.g. ice makers, hydroculator, etc.) and do not include an air gap or a listed integral backflow device.] |
09/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/25/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 1; SHEET TS.1: THE CODE CHECK INDICATES TWO EXITS ARE PROVIDED. PLEASE REVISE. 2. PREVIOUS COMMENT 2: ELEVATION 4B/A.3 STILL DOES NOT INDICATE A SINK. 3. GENERAL: PLEASE INDICATE ON THE DRAWINGS HOW THE REQUIREMENT OF THE IBC SECTION 3411.7 (MAXIMUM OF 20% OF PROJECT COST TO ACCESSIBILITY) IS MET. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
09/28/2015 | KROBLES1 | FIRE | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/28/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |