Permit Number: T15CM06501
Parcel: 121074810

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM06501
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the hazard rating for a hydroculator and verify that the proposed ASSE 1024-listed backflow preventer is appropriate. [Initial comment: Provide backflow protection for all appliances that are directly-connected to water (e.g. ice makers, hydroculator, etc.) and do not include an air gap or a listed integral backflow device.]
09/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/25/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1; SHEET TS.1: THE CODE CHECK INDICATES TWO EXITS ARE PROVIDED. PLEASE REVISE.
2. PREVIOUS COMMENT 2: ELEVATION 4B/A.3 STILL DOES NOT INDICATE A SINK.
3. GENERAL: PLEASE INDICATE ON THE DRAWINGS HOW THE REQUIREMENT OF THE IBC SECTION 3411.7 (MAXIMUM OF 20% OF PROJECT COST TO ACCESSIBILITY) IS MET.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/28/2015 KROBLES1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2015 KROBLES1 OUT TO CUSTOMER Completed