Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM06501
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/17/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
09/18/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/18/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A.1; FLOOR PLAN: THE CODE CHECK ON SHEET TS.1 INDICATES TWO EXITS ARE PROVIDED. THERE ARE SEVERAL EXITS SHOWN ON THE FLOOR PLAN, BUT ALL (EXCEPT FOR THE MAIN ENTRANCE) PASS THROUGH ADJOINING ROOMS. SHOW ON THE DRAWINGS HOW THE REQUIREMENTS OF SECTION 1014.2 ARE MET. 2. SHEET A.1 (FLOOR PLAN); ELEVATION 4B/A3: THE SINK INDICATED ON THE PLAN DOES NOT SHOW UP ON THE ELEVATION. PLEASE REVISE. 3. SHEET A.1; KEYNOTE 15: THE NOTE INDICATES A HANDICAP SINK, BUT ELEVATION 4B/A3 DOES NOT INDICATE AN ACCESSIBLE COUNTER HEIGHT. THIS IS NOT A PUBLIC SPACE, SO THE 3'-0" COUNTER HEIGHT IS ACCEPTABLE. REVISE THE KEYNOTE. 4. GENERAL: NEW EXIT SIGNAGE WILL BE REQUIRED TO DIRECT OCCUPANTS TO THE SECOND EXIT. PLEASE PROVIDE. 5. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 3411.6 ARE MET. 6. GENERAL: INDICATE ON THE DRAWINGS HOW THE REQUIREMENT OF THE IBC SECTION 3411.7(1) CONCERNING THE 20% MAXIMUM COST APPLIED TO ACCESSIBILITY IS MET. 7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
09/18/2015 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1. SHEET A.1; FLOOR PLAN: THE CODE CHECK ON SHEET TS.1 INDICATES TWO EXITS ARE PROVIDED. THERE ARE SEVERAL EXITS SHOWN ON THE FLOOR PLAN, BUT ALL (EXCEPT FOR THE MAIN ENTRANCE) PASS THROUGH ADJOINING ROOMS. SHOW ON THE DRAWINGS HOW THE REQUIREMENTS OF SECTION 1014.2 ARE MET. |
09/18/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide backflow protection for all appliances that are directly-connected to water (e.g. ice makers, hydroculator, etc.) and do not include an air gap or a listed integral backflow device. |
09/18/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the serial number of the water meter and the total demand that the meter serves. |
09/18/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |