Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM06501
Parcel: 121074810

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06501
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2015 STEVE SHIELDS ZONING REVIEW Approved
09/17/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
09/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A.1; FLOOR PLAN: THE CODE CHECK ON SHEET TS.1 INDICATES TWO EXITS ARE PROVIDED. THERE ARE SEVERAL EXITS SHOWN ON THE FLOOR PLAN, BUT ALL (EXCEPT FOR THE MAIN ENTRANCE) PASS THROUGH ADJOINING ROOMS. SHOW ON THE DRAWINGS HOW THE REQUIREMENTS OF SECTION 1014.2 ARE MET.
2. SHEET A.1 (FLOOR PLAN); ELEVATION 4B/A3: THE SINK INDICATED ON THE PLAN DOES NOT SHOW UP ON THE ELEVATION. PLEASE REVISE.
3. SHEET A.1; KEYNOTE 15: THE NOTE INDICATES A HANDICAP SINK, BUT ELEVATION 4B/A3 DOES NOT INDICATE AN ACCESSIBLE COUNTER HEIGHT. THIS IS NOT A PUBLIC SPACE, SO THE 3'-0" COUNTER HEIGHT IS ACCEPTABLE. REVISE THE KEYNOTE.
4. GENERAL: NEW EXIT SIGNAGE WILL BE REQUIRED TO DIRECT OCCUPANTS TO THE SECOND EXIT. PLEASE PROVIDE.
5. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 3411.6 ARE MET.
6. GENERAL: INDICATE ON THE DRAWINGS HOW THE REQUIREMENT OF THE IBC SECTION 3411.7(1) CONCERNING THE 20% MAXIMUM COST APPLIED TO ACCESSIBILITY IS MET.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/18/2015 MARTIN BROWN FIRE REVIEW Reqs Change 1. SHEET A.1; FLOOR PLAN: THE CODE CHECK ON SHEET TS.1 INDICATES TWO EXITS ARE PROVIDED. THERE ARE SEVERAL EXITS SHOWN ON THE FLOOR PLAN, BUT ALL (EXCEPT FOR THE MAIN ENTRANCE) PASS THROUGH ADJOINING ROOMS. SHOW ON THE DRAWINGS HOW THE REQUIREMENTS OF SECTION 1014.2 ARE MET.
09/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide backflow protection for all appliances that are directly-connected to water (e.g. ice makers, hydroculator, etc.) and do not include an air gap or a listed integral backflow device.
09/18/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the serial number of the water meter and the total demand that the meter serves.
09/18/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed