Permit Number: T15CM06497
Parcel: 11005314H

Address:
3175 N SWAN RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T15CM06497
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2015 MARTIN BROWN FIRE REVIEW Approved
10/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please verify voltages shown for all the equipment downsrteam of the 37.5 KVA transformer,on the one line diagram. Plan sheet E3. Shouldn't it be 240/120V.
Ref: IBC sec. 107.2.1, NEC
10/21/2015 DAVID RIVERA ZONING REVIEW Approved
10/21/2015 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
10/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/28/2015 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2015 KROBLES1 OUT TO CUSTOMER Completed