Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T15CM06454
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/30/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please be more specific or clarify as to the scope of electrical work to be performed for this project. The electrical plan notes on E2, E3, E4, seem to indicate "Proposed", or "Existing", or "Installed Under Separate Permit", for the same electrical service, generator, and associated equipment. The project description on the cover sheet T1 only addresses the placement of a premanufactured building. Ref IBC Sec. 107.2.1 |
| 10/07/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 10/12/2015 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | letter sent to records. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/16/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |