Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM06413
Parcel: 13316024L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06413
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2015 DAVID RIVERA ZONING REVIEW Approved
09/15/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the outside air requirements for the fan coils and coordinate with the Outside Air Ventilation Schedule.
2. Correct the labeling of the fan coil units.
09/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a updated panel schedule with designations for all new branch circuits, please address any load changes.
Ref: IBC 107.2.1, NEC art. 408.4
09/15/2015 JASON GREEN ENGINEERING REVIEW Approved
09/15/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/15/2015 ROBERT SHERRY WATER REVIEW Completed
09/15/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/15/2015 KEN BROUILLETTE FIRE REVIEW Approved
09/15/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed