Permit Review Detail
Review Status: Active
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM06366
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2015 | ANY | ENGINEERING | REVIEW | Active | |
| 10/23/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T15CM06366 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review. DIAGRAMS / CALCULATIONS 1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). The distribution panel bus and extended bus conductor (3) requires a rating for receiving electrical power from two sources. Show the panel rating and a minimum 41.7 AMP feeder rating when placed between source breakers of 20A & 30A. (41.7A conductor x 120% equal or greater than 20A + 30A), or move the backfeed breaker to the service panel. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 11/13/2015 | STEVE SHIELDS | ZONING | REVIEW | Needs Review |