Permit Number: T15CM06205
Parcel: 110060920

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM06205
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T15CM06205
4014 E. Monte Vista Drive
Residential (1st Review)

TRANSMITTAL DATE: September 8, 2015

The solar plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

1. The buildings are not shown correctly. The plan shows numerous detached structures when in fact they are all attached.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/08/2015 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: September 8, 2015
SUBJECT: Photovoltaic System
TO: SolarCity Corporation
REVIEWERS: Jason Green, CFM

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Site Plan for the installation of a photovoltaic system to an existing nonconforming structure at the above referenced property and does not recommend approval of the Site Plan at this time.

The subject property is located within a mapped FEMA Shaded Zone X 100-yr floodplain. Any improvements to the existing structure are considered a substantial improvement to an existing floodprone structure if the value of the new improvement is 50% or more than the assessed/appraised value of the existing structure. In order to help you permit the PV system we will need the following information from you.

1) Provide a cost estimate for the PV system installation to the existing structure showing fair market value of the material and labor. Please refer to the relative portions of the Handbook for Arizona Communities on Floodplain Management and the National Flood Insurance Program here; http://www.azwater.gov/azdwr/SurfaceWater/FloodManagement/documents/HandbookOct2000.pdf

2) Provide an assessed or appraised value of the existing single family. The assessed or appraised value is for the structure only (excluding land value). The assessed value can be provided by the latest assessment rolls of the county assessor prior to the improvements being started or from a licensed appraiser.

3) Provide a Floodplain Use Permit application with fees for review and approval on the next submittal.


GENERAL COMMENTS:

Please provide a cost estimate and the assessed or appraised value of the structure along with a comment letter that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

If you have any questions, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
09/16/2015 EGALLET1 BUILDING-RESIDENTIAL REVIEW Needs Review