Permit Number: T15CM06162
Parcel: 14126006H

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T15CM06162
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2015 KEN BROUILLETTE FIRE REVIEW Approved
09/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide for:
#1. Special inspection for exterior lighting as required per section 106.2.2 of the Tucson Outdoor Lighting Code.
#2. Electrical plans not sealed or stamped by a registered design professional.
Ref: IBC sec 107.2.1. Tucson Outdoor Lighting Code.
Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
09/24/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
09/24/2015 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
09/28/2015 FRODRIG2 COMMUNICATIONS REVIEW Reqs Change DENIAL LETTER SENT TO RECORDS.
09/28/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/28/2015 JASON GREEN ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2015 EGALLET1 APPROVAL SHELF Completed
11/03/2015 EGALLET1 OUT TO CUSTOMER Completed
11/03/2015 EGALLET1 REJECT SHELF Completed