Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM06094
Parcel: 12106261C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06094
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2015 STEVE SHIELDS ZONING REVIEW Approved
09/01/2015 JASON GREEN ENGINEERING REVIEW Approved
09/02/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
09/02/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/02/2015 MARTIN BROWN FIRE REVIEW Approved
09/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/02/2015 ROBERT SHERRY WATER REVIEW Completed
09/03/2015 EGALLET1 BUILDING-COMMERCIAL REVIEW Needs Review