Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Permit Number - T15CM06068
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/02/2015 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
| 12/07/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed | |
| 12/07/2015 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | Per section 507 of the 2012 International Fire Code, building must be within 600' of a fire hydrant. Additionally, the hydrant must be capable of providing 2000 GPM @ 20 PSI. Provide evidence of compliance with these requirements on plans, or indicate intent to install a fire sprinkler system. |