Permit Number: T15CM06064
Parcel: 13415001F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06064
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2015 STEVE SHIELDS ZONING REVIEW Approved
08/31/2015 LOREN MAKUS ENGINEERING REVIEW Approved
09/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical design as required to avoid using the egress corridors as return air ducts Reference: Section 601.2, IMC 2012.
09/01/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Approved
09/01/2015 ROBERT SHERRY WATER REVIEW Completed
09/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide structural details for the installation of the water heater, WH-1.
2. Revise detail 4/P.2 to refer to WH-1 instead of "WH-3 @ Maintenance Bldg."
09/02/2015 MARTIN BROWN FIRE REVIEW Approved
09/02/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed