Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM06064
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/31/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/31/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
09/01/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical design as required to avoid using the egress corridors as return air ducts Reference: Section 601.2, IMC 2012. |
09/01/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/01/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/01/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural details for the installation of the water heater, WH-1. 2. Revise detail 4/P.2 to refer to WH-1 instead of "WH-3 @ Maintenance Bldg." |
09/02/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
09/02/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |