Permit Number: T15CM06053
Parcel: 117130250

Address:
1 W BROADWAY BL

Review Status: Active

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T15CM06053
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2015 ANY ENGINEERING REVIEW Active
09/17/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 1 W. Broadway Blvd
T15CM06053
Building Plan (1st Review)

TRANSMITTAL DATE: September 17, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans cannot be approved until the development package, DP15-0053, has been approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/23/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. PLEASE UPDATE PROJECT MANUAL WITH CURRENT REFERENCES FOR NFPA.
2. IS PANIC HARDWARE GOING TO BE INSTALLED IN ELECTRICAL ROOMS/TRANSFORMER ROOMS PER IFC 1008.1.10?
3. I AM CONCERNED THAT ACCESS TO THE PENTHOUSE LEVEL WILL PUT THIS BUILDING UNDER THE HIGH RISE DEFINITION. PLEASE VERIFY THAT ACCESS TO THE HIGHEST LEVEL OR ROOF WILL NOT CHANGE THE DEFINITION OF THIS BUILDING TO A HIGH RISE.
4. PLEASE INDICATE STANDPIPES WILL BE INSTALLED PER THE IFC
09/28/2015 JASON GREEN ENGINEERING REVIEW Reqs Change Will approve the building plan upon approval of the DP
09/28/2015 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/28/2015 CPIERCE1 WATER REVIEW Needs Review
09/28/2015 CPIERCE1 DESIGN PROFESSIONAL REVIEW Needs Review
10/14/2015 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2016 AROMERO4 OUT TO CUSTOMER Completed