Permit Number: T15CM06000
Parcel: 12009308A

Address:
4823 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM06000
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2015 MARTIN BROWN FIRE REVIEW Approved
09/21/2015 DAVID RIVERA ZONING REVIEW Approved
09/21/2015 DAVID RIVERA ADA REVIEW Approved
09/28/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S4 (DETAIL 2); STRUCTURAL CALCULATIONS (SHEET 14): THE CALCULATIONS INDICATE A 14" DIAMETER X 3'-6" DEEP POST FOUNDATION, WHILE THE DETAIL INDICATES A 12" DIAMETER X 3'-6" DEEP FOUNDATION. PLEASE CLARIFY.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2015 EGALLET1 OUT TO CUSTOMER Completed