Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. STRUCTURAL CALCULATIONS (SCHNEIDER): NOTE 1 ON THE COVER LETTER INDICATES THE 20 PSF ROOF LIVE LOAD REDUCES TO 0 UNDER THE NEW SOLAR PANELS. THE CITY OF TUCSON WILL ALLOW LIVE LOAD REDUCTIONS PER THE IBC SECTION 1607.12.2, BUT REMOVAL OF THE ENTIRE ROOF LIVE LOAD IS NOT AN ACCEPTABLE PRACTICE. PLEASE VERIFY.
2. GENERAL: PLEASE PROVIDE A WRITTEN RESPONSE TO THE REVIEW COMMENT.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2015 ANY REJECT SHELF RECEIVED