Permit Number: T15CM05954
Parcel: 10409032F

Address:
4215 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05954
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change As per the last electrical plan review comment #2. Per the lighting schedule on plan sheet E1.0, the new exterior luminaires "OA" seem to be in violation of sec. 402.1 ( color temp. ) cannot exceed 3500K.
11/04/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/13/2015 ROBERT SHERRY WATER REVIEW Completed
11/13/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The Bradley HL-series thermostatic mixing valves are ASSE 1017 certified and, according to the manufacturer's installation literature, these valves "…should not be used where ASSE 1016, 1069, or 1070 devices are required. These valves should never be used to provide "anti-scald" or "anti-chill" service." [Initial comment: Verify that the specified point of use mixing valves for the restroom lavatories conform to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.]