Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM05954
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | As per the last electrical plan review comment #2. Per the lighting schedule on plan sheet E1.0, the new exterior luminaires "OA" seem to be in violation of sec. 402.1 ( color temp. ) cannot exceed 3500K. |
| 11/04/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/13/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 11/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The Bradley HL-series thermostatic mixing valves are ASSE 1017 certified and, according to the manufacturer's installation literature, these valves "…should not be used where ASSE 1016, 1069, or 1070 devices are required. These valves should never be used to provide "anti-scald" or "anti-chill" service." [Initial comment: Verify that the specified point of use mixing valves for the restroom lavatories conform to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.] |