Permit Number: T15CM05954
Parcel: 10409032F

Address:
4215 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05954
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide the following information:
#1. Complete panel schedules for panelboard 'B', and smart panels 'A' and 'B'.
#2. Compliance with the Tucson Outdoor Lighting Code.
Ref; IBC sec. 107.2.1, NEC art.408
10/06/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
10/07/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the specified point of use mixing valves for the restroom lavatories conform to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
10/07/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CS1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CODE INFORMATION.
2. SHEET CS1.0 (NUMBER OF EXITS); SHEET A0.1 (LIFE SAFETY PLAN): THE CODE INFORMATION ON SHEET CS1.0 INDICATES THREE EXITS ARE PROVIDED. EXIT THREE ON THE LIFE SAFETY PLAN CAN ONLY BE CONSIDERED AN EXIT IF ALL OF THE CRITERIA OF THE IBC SECTION 1014.2(4)(2) ARE MET. PLEASE VERIFY AND INDICATE ON THE PLAN.
3. SHEET CS1.0; CODE INFORMATION: PLEASE INDICATE ON THE DRAWINGS THE SPRINKLER SYSTEM REQUIRED IN THIS SPACE PER THE IBC SECTION 903.3.
4. SHEET CS1.0; CODE INFORMATION: THE NUMBER OF EXITS REQUIRED REFERENCES THE IBC TABLE 1009.1. PLEASE REVISE THE REFERENCE.
5. SHEET CS1.0; CODE INFORMATION: THE MAXIMUM TRAVEL DISTANCE TO AN EXIT REFERENCES THE IBC TABLE 1016.1 IN TWO LOCATIONS. PLEASE REVISE THE REFERENCES.
6. SHEET CS1.0; CODE INFORMATION: THE MAXIMUM DEAD END TRAVEL DISTANCE REFERENCES THE IBC SECTION 1017.3. PLEASE REVISE THE REFERENCE AND REVISE THE DISTANCE PER THE IBC SECTION 1018.4(2).
7. SHEET CS1.0; CODE INFORMATION: THE AISLE WIDTHS REFERENCE THE IBC SECTION 1017.2. PLEASE REVISE THE REFERENCE.
8. SHEET CS1.0; CODE INFORMATION: THE PLUMBING FIXTURE REQUIREMENTS REFERENCES 364 OCCUPANTS, WHILE A PREVIOUS TABLE ON THIS SHEET INDICATES 348 OCCUPANTS. PLEASE COORDINATE.
9. SHEET CS1.0; CODE INFORMATION: THE PLUMBING FIXTURE REQUIREMENTS TABLE INDICATES NO SERVICE SINKS ARE REQUIRED. PLEASE REVISE THAT PER THE IBC TABLE 2902.1.
10. SHEET CS1.0; CODE INFORMATION: A NARRATIVE LOCATED UNDER THE PLUMBING FIXTURE TABLE REFERENCES 'TOILET FACILITIES IN ASSEMBLY OCCUPANCIES'. REVISE THAT PARAGRAPH TO REFERENCE RETAIL OCCUPANCIES.
11. SHEET CS1.0; CODE INFORMATION: THE EGRESS DOOR CONTROLS REFERENCES THE IBC SECTION 1008.1.4.4. PLEASE REVISE THE REFERENCE NUMBER.
12. SHEET A0.1; LIFE SAFETY PLAN: PER THE IBC SECTION 1105.1, AT LEAST 60% OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE. VERIFY THAT REQUIREMENT IS MET ON THIS PLAN.
13. SHEET A0.1; EGRESS WIDTH REQUIRED TABLE: THE MINIMUM NUMBER OF EXITS INDICATES '2 ACCESSIBLE EXITS'. PLEASE CLARIFY THAT EXITS ONE AND TWO ARE ACCESSIBLE.
14. SHEET A0.1: A SHEET NOTE INDICATES THE PROJECT IS TO BE CONSTRUCTED PER THE 2012 IRC. PLEASE REVISE.
15. SHEETS A0.1, A1.0, A1.1, A1.2, A1.3, AND A2.0: PLEASE INDICATE A NORTH ARROW ON THE PLANS.
16. THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES AND DIMENSIONS.
17. SHEET A1.2; ENLARGED FLOOR PLAN: THE ENLARGED PLAN REFERENCED AT THE UPPER RIGHT CORNER OF THE PLAN INDICATES 1/A1.4. PLEASE REVISE THE SHEET REFERENCE (NO SHEET A1.4).
18. SHEET A1.3; LINTEL SECTIONS: DO THE DRAWINGS INDICATE WHERE LINTEL SECTIONS A, B, AND C ARE USED? PLEASE VERIFY.
19. SHEET A1.3; LINTEL SECTIONS: WHAT ARE THE STRUCTURAL STEEL MEMBER SIZES INDICATED ON A, B, AND C? PLEASE PROVIDE STRUCTURAL CALCULATIONS WHERE THE LINTELS ARE NEW.
20. SHEET A1.3; SECTION 6: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES.
21. SHEET A1.3; ENLARGED FLOOR PLAN 1: A SECTION 2/A1.3 IS CUT TWICE ON THIS PLAN. PLEASE ADD SECTION 2 TO SHEET A1.3.
22. SHEET A1.3; ENLARGED FLOOR PLAN 1: PLEASE CUT SECTION 4/A1.3 ON THE PLAN.
23. SHEET A1.3; INTERIOR ELEVATION 4: A NOTE INDICATES 'G.C. TO FIELD VERIFY EXISTING CONCRETE FOUNDATION DESIGN'. THE G.C. IS RESPONSIBLE FOR IDENTIFYING THE SIZE OF THE EXISTING FOUNDATION, BUT THE ENGINEER/ARCHITECT OF RECORD IS RESPONSIBLE FOR THE DESIGN. PROVIDE STRUCTURAL CALCULATIONS FOR EXISTING FOUNDATIONS, BEAMS, COLUMNS, WALLS, ETC. AS REQUIRED.
24. SHEET A4.0; SECTIONS 1A, 1B, AND 5: PLEASE REFERENCES SHEET A6.1 FOR PARTITION BRACING.
25. SHEET A4.0; SECTION 2: A DETAIL CUT ON THE SECTION INDICATES 1-J/A6.1. PLEASE REVISE THE DETAIL NUMBER (NO J DETAIL).
26. SHEET A4.1; ELEVATIONS: PLEASE INDICATE THE ELEVATIONS ON THE CONSTRUCTION PLAN (A1.1).
27. SHEET A4.1; ELEVATIONS: PLEASE VERIFY THE INTERIOR ELEVATIONS ARE CORRECT AS SHOWN AND THE ELEVATION TITLES MATCH THE PLAN.
28. SHEET A5.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE ACCESSORY SCHEDULE SYMBOLS ON PLANS AND IN THE TABLE.
29. SHEET A6.0 (DOOR SCHEDULE); SHEET A7.1 (DIVISION 08): GENERAL NOTE 1 INDICATES TO 'REFER TO DIVISION 08 SECTION "DOOR HARDWARE" FOR HARDWARE SETS'. DIVISION 08 ON SHEET A7.1 LISTS NO DOOR HARDWARE. PLEASE CLARIFY.
30. SHEET A6.0; DOOR SCHEDULE: DOOR 22 LISTS NO HARDWARE. PLEASE PROVIDE.
31. SHEETS A6.1 AND A6.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DETAIL NOTES.
32. SHEET A6.1; PARTITION TYPE B: A NOTE AT THE DIAGONAL BRACE INDICATES DETAIL 2/A6.1. PLEASE REVISE THE DETAIL REFERENCE.
33. SHEET A6.1; SECTION 4: MOVE THE CLIP ANGLE DETAIL OUT OF THE VERBIAGE.
34. SHEETS A7.0, A7.1, A7.2, AND A7.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SPECIFICATIONS.
35. GENERAL: PER THE IBC SECTION 1110, SIGNAGE AT ACCESSIBLE ENTRANCES AND EXITS (WHERE NOT ALL ENTRANCES/EXITS ARE ACCESSIBLE) REQUIRES SIGNAGE. PLEASE INDICATE ON THE PLAN.
36. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/07/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the proposed HVAC units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
2. Verify that the specified building control system provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Provide thermal load and HVAC equipment-sizing calculations to confirm the specified heat pumps for each apartment type. Reference: Section R403.6, IECC 2012.
4. Show the size, routing, and termination of the condensate drains. Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (e.g. the roof). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
5. Show how ventilation air is being provided for the office, IT room, and the cash room. Reference: Section 403.2, IMC 2012.
6. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.
7. Verify that the distribution of supply air from the HVAC units during the heating season complies with the requirements of footnote (g) of Table 403.3.1.2, IMC 2012 or use a zone air distribution effectiveness value of 0.8 for the ventilation calculations. Reference: Section 403.3.1.2, IMC 2012.
8. Ventilation calculations for HVAC systems supplying multiple zones (e.g. RTU-7 and RTU-8) shall take into account the different occupancy loads in each zone. Reference: Section 403.3.2.3, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2015 EGALLET1 APPROVAL SHELF Completed
10/09/2015 FERNE RODRIGUEZ REJECT SHELF Completed