Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2015 LOREN MAKUS ENGINEERING REVIEW Reqs Change Building plans will be approved once the development package is approved.
11/25/2015 ROBERT SHERRY WATER REVIEW Completed
11/25/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revised COMcheck Envelope Compliance report was not included with this submittal. [Initial comment: Provide NFRC fenestration product ratings for the U-factor of the uninsulated swinging door on COMcheck or use the appropriate default U-factor from Table C303.1.3 (2), IECC 2012. Reference: Section C303.1.3, IEC 2012.]
2. Revised COMcheck Envelope Compliance report was not included with this submittal. [Initial comment: The CPD number for Window 1 in the Envelope Compliance Certificate was not recognized by the NFRC web site. Provide the manufacturer's literature that shows the NFRC data. Reference: Section C303.1.3, IECC 2012.]
11/27/2015 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/30/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change Date: 11-30-15
Activity: T15CM05936 2nd review
Address: 8005 E. Speedway Blvd.
Applicant: Metro TED

Previous Comment for Sheet D1.0
1. Please clarify reference numbers to the enlarged demo plan. Should this be detail 1 or detail 2?
Note: There are two drawings labeled #1 and the reference is to drawing #2. Please revise

Previous Comments for Sheet A1.0
2. Clarify wall reference -/A5.1 as indicated on wall type 6S.
Note: There should be a detail number where the dash is located on this reference. Please revise

General Note:
The occupancy type and area information has been modified on sheet TS1.0. This change will affect the permit valuation.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
12/03/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Mesquite Valley Growers Nursery
T15CM05936
Building Plan (2nd Review)

TRANSMITTAL DATE: December 3, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the plans match development package DP14-0200 but cannot be approved until the development package, has been approved.

3. Zoning will not approve until all other PDSD agencies have approved the building plan.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956