Permit Number: T15CM05936
Parcel: 13309064A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM05936
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2015 JASON GREEN ENGINEERING REVIEW Reqs Change Will approve the building plan upon approval of the development package, DP14-0200. JG
09/08/2015 KEN BROUILLETTE FIRE REVIEW Approved
09/14/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Mesquite Valley Growers Nursery
T15CM05936
Building Plan (1st Review)

TRANSMITTAL DATE: September 15, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the plans match development package DP14-0200 but cannot be approved until the development package, has been approved.

3. Zoning will not approve until all other PDSD agencies have approved the building plan.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/15/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN REVIEW COMMENTS
Date: 9-16-15
Activity: T15CM05936
Address: 8005 E. Speedway Blvd.
Applicant: Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

Sheet D1.0
1. Please clarify reference numbers to the enlarged demo plan. Should this be detail 1 or detail 2?

Sheet A0.1
2. Correct the allowable tabular floor area for the M occupancy. 6,000 square feet indicated but 9,000 used, Table 503.
3. Please clarify all square footage values indicated for proposed buildings. The values in the code analysis are not consistent with values provided elsewhere on the drawings.
4. Provide a minimum 1-hour fire-rated construction for buildings of U occupancies located within five (5) feet from the fire separation line, Table 602.
5. Provide a minimum 2-hour fire-rated construction for buildings of M occupancies located within five (5) feet from the fire separation line, Table 602.
6. Provide a code analysis for the partially demolished building located on the north end of the complex to include occupancy type, egress plan, fire separation, maximum occupant load, and minimum plumbing fixtures, 102.2.1. Note: additional review comments may apply due to lack of information provided.

Sheet A1.0
7. Please include fire-rated wall construction types on wall type schedule, 705.3.
8. Clarify wall reference -/A5.1 as indicated on wall type 6S.
9. Clarify keynote 15.1. Detail 6 could not be located on sheet A3.
10. Remove all keynotes that do not apply to this project. Approximately twenty (20) keynotes could not be located on any of the drawings.
11. Indicate the locations of all portable fire extinguishers, 906.3

Sheet A1.1
12. Indicate the locations of all portable fire extinguishers, 906.3

Sheet A1.2
13. Please enlarge the viewport window for drawing number 1 to include the left side of the drawing.
14. Correct the mislabeled elevation reference number located in room 110 on drawing number 3.

Sheet A2.1
15. Provide an exit sign for the exterior door located on the north end of the greenhouse, 1011.1.

Sheet A5.0
16. Specify fire-rated doors in all fire-rated wall assemblies, 705.8.2.
17. Specify fire-rated glazing in all fire-rated wall assemblies, 705.8.2.

All Structural Sheets
18. Provide structural calculations for the primary M occupancy building. Calculations were only provided for the greenhouse buildings. Note: structural review has not been completed to lack of information provided. Additional comments may apply.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
09/18/2015 ROBERT SHERRY WATER REVIEW Reqs Change Clarify the size of the water meter that will be serving the new building; the civil utility drawing calls for a new 1-1/2" meter, sheet P1.0 shows a 1-1/2" meter and the pressure loss calculations on P2.0 reference an existing 2" meter.
09/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/21/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/28/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide NFRC fenestration product ratings for the U-factor of the uninsulated swinging door on COMcheck or use the appropriate default U-factor from Table C303.1.3 (2), IECC 2012. Reference: Section C303.1.3, IEC 2012.
2. The CPD number for Window 1 in the Envelope Compliance Certificate was not recognized by the NFRC web site. Provide the manufacturer's literature that shows the NFRC data. Reference: Section C303.1.3, IECC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
10/12/2015 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2015 AROMERO4 OUT TO CUSTOMER Completed