Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T15CM05877
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/03/2015 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1. SHEET A3.0-DOOR 102 HARDWARE LIST SET 1, SET 1 HAS THREE TYPES OF LOCK SETS LISTED ON PLANS. FOR AN ASSEMBLY OCCUPANCY IT SHOULD BE PANIC HARDWARE AND NO OTHER LOCK OR LATCH. PLEASE REVISE. 2. A3.0- DOOR 100 LIST "EXISTING HARDWARE" I NEED TO KNOW WHAT THE EXISTING HARDWARE IS TO DETERMINE IF CODE COMPLIANT. 3. WHAT IS THE OCCUPANT LOAD? IT IS LISTED WITH TWO DIFFERENT NUMBERS ON TWO DIFFERENT PAGES. 4. SHEET A2.0-ARE THE STOOLS FIXED? 5. SHEET A1.1 EMERGENCY LIGHTING SYMBOL SHOWN ON LEDGEND. I COULD NOT FIND THE SYMBOL LISTED ANYWHERE AND COULD NOT FIND ANY EMERGENCY LIGHTING LISTED ON ELECTRICAL PLANS. PLEASE HELP ME WITH THIS ONE IF I AM MISSING SOMETHING. 6. SHEET A2.0-WHAT IF ANY HARDWARE IS GOING TO BE ON GATES? IF YOU DO NOT KNOW, THEN MAKE A NOTE THAT THE GATES NEED TO SWING OUT IN THE DIRECTION OF TRAVEL AND NO HARDWARE IS ALLOWED UNLESS IT MEETS THE IFC FOR EXITING.-REVIEWED BY KEN BROUILLETTE |
09/04/2015 | ROBERT SHERRY | WATER | REVIEW | Completed |