Permit Number: T15CM05817
Parcel: 140420740

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05817
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2015 DAVID RIVERA ZONING REVIEW Passed
08/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/20/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete panel schedules for 'AATP' and 'CAOP',load calc's, include a feeder schedule for the new or replaced panels.
Ref: IBC sec 107.2.1, NEC, art.110.3, 408.4.
08/20/2015 JASON GREEN ENGINEERING REVIEW Approved
08/20/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
08/20/2015 ROBERT SHERRY WATER REVIEW Completed
08/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show that the hot water source is within 50-feet of the new breakroom sink. Reference: Section 607.2, IPC 2012.
08/20/2015 KEN BROUILLETTE FIRE REVIEW Approved
08/20/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed