Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05817
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/20/2015 | DAVID RIVERA | ZONING | REVIEW | Passed | |
08/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
08/20/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete panel schedules for 'AATP' and 'CAOP',load calc's, include a feeder schedule for the new or replaced panels. Ref: IBC sec 107.2.1, NEC, art.110.3, 408.4. |
08/20/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
08/20/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/20/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show that the hot water source is within 50-feet of the new breakroom sink. Reference: Section 607.2, IPC 2012. |
08/20/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
08/20/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |