Permit Number: T15CM05737
Parcel: 14029037B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05737
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2015 STEVE SHIELDS ZONING REVIEW Approved
08/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a maint. receptacle on the roof for the new HP-1 unit as required per NEC.
08/18/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
08/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1 (CODE REVIEW CHECKLIST); SHEET A3 (FLOOR PLAN): PROVIDE A CALCULATION ON THE DRAWINGS FOR THE OCCUPANT LOAD DETERMINATION FOR THIS PROJECT.
2. SHEET T1; EXIT PLAN: PLEASE INDICATE THE EXIT ACCESS TRAVEL DISTANCES ON THIS PLAN PER THE IBC SECTION 1016, AND VERIFY THESE DISTANCES MEET THE CODE REQUIREMENTS.
3. SHEET A3 (FLOOR PLAN); SHEET E1 (FLOOR PLAN): AT THE NEW OPENING IN THE WALL, EXIT SIGNAGE IS REQUIRED PER THE IBC SECTION 1011. PLEASE PROVIDE ON THE DRAWINGS. NEW SIGNAGE MUST ALSO INDICATE DIRECTION FROM THE NEW SPACE TO THE SECOND EXIT.
4. SHEET A3; FLOOR PLAN: AT THE NEW OPENING IN THE WALL, PROVIDE A HEADER SIZE AND DETAILS ON THE DRAWINGS.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/18/2015 ROBERT SHERRY WATER REVIEW Completed
08/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change If the showers do not have pre-fabricated receptors, provide details to show that the construction of the receptors complies with the requirements of Section 417.5.2, IPC 2012.
08/18/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/19/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change Same as building review comments