Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2015 ROBERT SHERRY WATER REVIEW Completed
09/17/2015 MARTIN BROWN FIRE REVIEW Reqs Change Sheet a5.1- door 106A Keynote states Panic Hardware but Hardware Set F indicates no latch. I don't understand.

Sheet 3.0 indicates door 106a swings in both directions. It should only swing in the direction of egress for exiting.

Sheet 4.0 Reflective ceiling plan does not show exit signage over door 106a. I also checked the electrical plans too for the sign.

Please correct and resubmit to Stantec and City for review, re-stamps and approval.-Ken Brouillette