Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05599
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 08/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/13/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/13/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following; #1.Please show all feeder,conduit,conductor sizes,types between the ATS for the elevator and panel 'GEN'. #2. The stepdown transformer for panel 'GEN' are shown with different KVA ratings on the plans. #3. Please clarify in detail the installation and wiring methods to provde compliance with 695.6A2 as per the note on plan sheet 'E2.0, for the fire pump feeder from the generator. #4. Provide Grounding Electrode information on the plans for the transformer. As required per NEC art.250. #4. Please verify that the feeder sizes specified for the normal power via bus plug to the elevator ATS are correct. #5. Provide for warning labels at all required locations as required per NEC art's 700,701,702. |
| 08/13/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/14/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/14/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PROVIDE SIGNATURE AND SEAL OF THE STRUCTURAL ENGINEER ON THE CALCULATIONS. 2. PROVIDE SPECIAL INSPECTION FORM FOR FIELD WELDING AND HIGH STRENGTH BOLTS. |
| 09/23/2015 | EGALLET1 | FIRE | REVIEW | Needs Review |