Permit Number: T15CM05599
Parcel: 117066840

Address:
55 N 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05599
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2015 LOREN MAKUS ENGINEERING REVIEW Passed
08/13/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
08/13/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/13/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following;
#1.Please show all feeder,conduit,conductor sizes,types between the ATS for the elevator and panel 'GEN'.
#2. The stepdown transformer for panel 'GEN' are shown with different KVA ratings on the plans.
#3. Please clarify in detail the installation and wiring methods to provde compliance with 695.6A2 as per the note on plan sheet 'E2.0, for the fire pump feeder from the generator.
#4. Provide Grounding Electrode information on the plans for the transformer. As required per NEC art.250.
#4. Please verify that the feeder sizes specified for the normal power via bus plug to the elevator ATS are correct.
#5. Provide for warning labels at all required locations as required per NEC art's 700,701,702.
08/13/2015 ROBERT SHERRY WATER REVIEW Completed
08/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/14/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PROVIDE SIGNATURE AND SEAL OF THE STRUCTURAL ENGINEER ON THE CALCULATIONS.
2. PROVIDE SPECIAL INSPECTION FORM FOR FIELD WELDING AND HIGH STRENGTH BOLTS.
08/14/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/23/2015 EGALLET1 FIRE REVIEW Needs Review