Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05528
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1. The plans submitted state under the General Building Summary that a NFPA 13D is installed. Per documentation submitted and from the approved and completed permit T15BU00544 the design is for a NFPA 13R system. Please clarify if this was missed on sheet G-1 by the Architect. 2. Fire will wait to see the results of the requested Board of Appeals Hearing and then continue the plan review upon receipt of resumbittal drawings. |
| 11/19/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; SPACE PLAN: PER THE IBC SECTION 420.2 (INCLUDING SECTION 310.6 THAT REQUIRES R4 OCCUPANCIES TO MEET THE REQUIREMENTS FOR CONSTRUCTION AS DEFINED FOR GROUP R3), WALLS SEPARATING DWELLING UNITS, SLEEPING UNITS, AND DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES SHALL BE CONSTRUCTED AS FIRE PARTITIONS. PER THE IBC SECTION 708.3, THIS WOULD REQUIRE A ONE HOUR RATED WALL AT THOSE LOCATIONS. AS A SUGGESTION, AN APPEAL TO THE BUILDING OFFICIAL CONCERNING THE WALL FIRE RESISTANCE RATINGS MIGHT BE AN OPTION. 2. SHEET A1; SPACE PLAN: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 3411.4.2 ARE MET FOR THIS PROJECT. 3. SHEET A1; SPACE PLAN: PLEASE INDICATE ON THE DRAWINGS HOW THE REQUIREMENT OF THE IBC SECTION 3411.7(1) IS APPLIED TO THIS PROJECT, INCLUDING THE ITEM DESCRIPTION AND IT'S COST. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/19/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/19/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/19/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 11/19/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/30/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | Verify that the water service to the building is protected by a reduced pressure backflow prevention assembly. Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/03/2015 | EGALLET1 | APPROVAL SHELF | Completed |
| 12/03/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |
| 12/03/2015 | EGALLET1 | REJECT SHELF | Completed |