Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05526
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/11/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/11/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following; #1. Complete one line diagram including load calc's, AIC, Feeder and conduit sizes, types,overcurrent protection. #2. Compliance with IECC for interior lighting. #3. Assigned circuiting for all Receptacles, light fixtures. #4. All receptacles at food prep areas to be GFI protected. #5. Min. font size 3/32". #6. Complete light fixture schedule. |
| 08/11/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 08/11/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/11/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/11/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/11/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/12/2015 | AROMERO4 | ZONING | REVIEW | Needs Review |